Section 6
1MAC309294-MB F
Condition monitoring functions
368
RER620
Technical Manual
Figure 202:
Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals
PRES_LO_IN
and
PRES_ALM_IN
.
Timer 1
When the
PRES_ALM_IN
binary input is activated, the
PRES_ALM
alarm is activated
after a time delay set with the
Pressure alarm time
setting. The
PRES_ALM
alarm can be
blocked by activating the
BLOCK
input.
Timer 2
If the pressure drops further to a very low level, the
PRES_LO_IN
binary input becomes
high, activating the lockout alarm
PRES_LO
after a time delay set with the
Pres lockout
time
setting. The
PRES_LO
alarm can be blocked by activating the
BLOCK
input.
6.1.5
Application
52CM includes different metering and monitoring subfunctions.
Circuit breaker status
Circuit breaker status monitors the position of the circuit breaker, that is, whether the
breaker is in an open, closed or intermediate position.
Circuit breaker operation monitoring
The purpose of the circuit breaker operation monitoring is to indicate that the circuit
breaker has not been operated for a long time. The function calculates the number of days
the circuit breaker has remained inactive, that is, has stayed in the same open or closed
state. There is also the possibility to set an initial inactive day.
Breaker contact travel time
High travelling times indicate the need for maintenance of the circuit breaker mechanism.
Therefore, detecting excessive travelling time is needed. During the opening cycle
operation, the main contact starts opening. The auxiliary contact A opens, the auxiliary
contact B closes, and the main contact reaches its opening position. During the closing
cycle, the first main contact starts closing. The auxiliary contact B opens, the auxiliary
contact A closes, and the main contact reaches its close position. The travel times are
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......