1MAC309294-MB F
Section 4
Protection functions
RER620
125
Technical Manual
4.1.3.2
Function block
Figure 55:
Function block
4.1.3.3
Functionality
The ground-fault function 51N/50N or 51G/50G is used as non-directional ground-fault
protection for feeders.
The function picks up and trips when the measured (IG) or calculated (IN) ground current
exceeds the set limit. The trip time characteristic for low stage 51N/G and high stage
50N/G-1/2 can be selected to be either definite time (DT) or inverse definite minimum
time (IDMT). The instantaneous stage 50N/G-3 always trips with the DT characteristic.
In the DT mode, the function trips after a predefined trip time and resets when the fault
current disappears. The IDMT mode provides current-dependent timer characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself, if desired.
4.1.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of non-directional ground-fault protection can be described by using a
module diagram. All the blocks in the diagram are explained in the next sections.
Figure 56:
Functional module diagram. I
0
represents the residual current.
Level detector
The measured ground current is compared with the set
Pickup value
.and, if enabled, the
Pickup block value
. If the measured value exceeds the set
Pickup value
, and is less than
the
Pickup block value
, the level detector sends an enable-signal to the timer module. If
the
ENA_MULT
input is active, the
Pickup value
setting is multiplied by the
Pickup value
Mult
setting.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......