Section 6
1MAC309294-MB F
Condition monitoring functions
372
RER620
Technical Manual
6.1.6
Signals
Table 326: 52CM Input signals
Table 327: 52CM Output signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block input status
POSOPEN_A
BOOLEAN
0=False
Signal for open position of apparatus from I/O, phase A
POSOPEN_B
BOOLEAN
0=False
Signal for open position of apparatus from I/O, phase B
POSOPEN_C
BOOLEAN
0=False
Signal for open position of apparatus from I/O, phase C
POSCLOSE_A
BOOLEAN
0=False
Signal for close position of apparatus from I/O, phase A
POSCLOSE_B
BOOLEAN
0=False
Signal for close position of apparatus from I/O, phase B
POSCLOSE_C
BOOLEAN
0=False
Signal for close position of apparatus from I/O, phase C
PRES_ALM_IN
BOOLEAN
0=False
Binary pressure alarm input
PRES_LO_IN
BOOLEAN
0=False
Binary pressure input for lockout indication
SPR_CHR_ST
BOOLEAN
0=False
CB spring charging started input
SPR_CHR
BOOLEAN
0=False
CB spring charged input
RST_IPOW
BOOLEAN
0=False
Reset accumulation energy
RST_CB_WEAR
BOOLEAN
0=False
Reset input for CB remaining life and operation counter
RST_TRV_T
BOOLEAN
0=False
Reset input for CB closing and opening travel times
RST_SPR_T
BOOLEAN
0=False
Reset input for the charging time of the CB spring
Name
Type
Description
TRV_T_OP_ALM
BOOLEAN
CB open travel time exceeded set value
TRV_T_CL_ALM
BOOLEAN
CB close travel time exceeded set value
SPR_CHR_ALM
BOOLEAN
Spring charging time has crossed the set value
OPR_ALM
BOOLEAN
Number of CB operations exceeds alarm limit
OPR_LO
BOOLEAN
Number of CB operations exceeds lockout limit
IPOW_ALM
BOOLEAN
Accumulated currents power (Iyt) exceeded alarm limit
IPOW_LO
BOOLEAN
Accumulated currents power (Iyt) exceeded lockout limit
CB_LIFE_ALM
BOOLEAN
Remaining life of CB exceeded alarm limit
MON_ALM
BOOLEAN
CB ' not operated for long time ' alarm
PRES_ALM
BOOLEAN
Pressure below alarm level
PRES_LO
BOOLEAN
Pressure below lockout level
OPENPOS_A
BOOLEAN
CB is in open position, phase A
OPENPOS_B
BOOLEAN
CB is in open position, phase B
OPENPOS_C
BOOLEAN
CB is in open position, phase C
INVALIDPOS_A
BOOLEAN
CB is in invalid position (not positively open or closed), phase A
INVALIDPOS_B
BOOLEAN
CB is in invalid position (not positively open or closed), phase B
INVALIDPOS_C
BOOLEAN
CB is in invalid position (not positively open or closed), phase C
CLOSEPOS_A
BOOLEAN
CB is in closed position, phase A
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......