1MAC309294-MB F
Section 4
Protection functions
RER620
199
Technical Manual
The level detector contains a low-level blocking functionality for cases where one of the
measured voltages is below the desired level. This feature is useful when unnecessary
pickups and trips are wanted to avoid during, for example, an autoreclose sequence. The
low-level blocking is activated by default (
Enable block value
is set to “True”) and the
blocking level can be set with the
Voltage block value
setting.
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects the
phase or phases in which the fault level is detected. If the number of faulty phases match
with the set
Num of pickup phases
, the phase selection logic activates the timer.
Timer
Once activated, the timer activates the
PICKUP(START)
output. Depending on the value
of the set
Operating curve type
, the time characteristics are selected according to DT or
IDMT.
When the operation timer has reached the value set by
Trip delay time
in the DT mode or
the maximum value defined by the IDMT, the
TRIP (OPERATE)
output is activated.
When the user-programmable IDMT curve is selected, the trip time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation occurs, that is, a fault suddenly disappears before the trip delay is
exceeded, the reset state is activated. The behavior in the drop-off situation depends on the
selected trip time characteristics. If the DT characteristics are selected, the reset timer runs
until the set
Reset delay time
value is exceeded. If the drop-off situation exceeds the set
Reset delay time
, the timer is reset and the
PICKUP
output is deactivated.
When the IDMT trip time curve is selected, the functionality of the timer in the drop-off
state depends on the combination of the
Type of reset curve
and
Reset delay time
settings.
For a detailed description of the voltage IDMT curves, see the General
function block features section in this manual.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......