1MAC309294-MB F
Section 6
Condition monitoring functions
RER620
361
Technical Manual
Figure 194:
Functional module diagram for calculating inactive days and alarm for
circuit breaker operation monitoring
Inactivity timer
The module calculates the number of days the circuit breaker has remained inactive, that
is, has stayed in the same open or closed state. The calculation is done by monitoring the
states of the
POSOPEN_A(_B,_C)
and
POSCLOSE
auxiliary contacts.
The inactive days is available through the Monitored data view. It is also possible to set
the initial inactive days by using the parameter.
Alarm limit check
When the inactive days exceed the limit value defined with the setting, the alarm is
initiated. The time in hours at which this alarm is activated can be set with the parameter
as coordinates of UTC. The alarm signal can be blocked by activating the binary input
BLOCK
.
6.1.4.3
Breaker contact travel time
The breaker contact travel time module calculates the breaker contact travel time for the
closing and opening operation. The operation of the breaker contact travel time
measurement can be described by using a module diagram. All the modules in the diagram
are explained in the next sections.
Inactivity
timer (A)
POSOPEN_A
POSCLOSE_A
BLOCK
Alarm limit
check
MON_ALM
Inactivity
timer (B)
POSOPEN_B
POSCLOSE_B
Inactivity
timer (C)
POSOPEN_C
POSCLOSE_C
This subfunction requires two position inputs
POSOPEN_A(_B,_C)
and
POSCLOSE_A(_B,_C)
from the circuit breaker.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......