Section 4
1MAC309294-MB F
Protection functions
230
RER620
Technical Manual
loads to stabilize the network. Thus, loads are normally prioritized so that the less
important loads are shed before the important loads.
During the operation of some of the protective schemes or other system emergencies, the
power system is divided into small islands. There is always a load - generation imbalance
in such islands that leads to a deviation in the operating frequency from the nominal
frequency. This off-nominal frequency operation is harmful to power system components
like turbines and motors. Therefore, such situation must be prevented from continuing.
The frequency-based load-shedding scheme should be applied to restore the operation of
the system to normal frequency. This is achieved by quickly creating the load - generation
balance by disconnecting the load.
As the formation of the system islands is not always predefined, several load-shedding
relays are required to be deployed at various places near the load centers. A quick shedding
of a large amount of load from one place can cause a significant disturbance in the system.
The load-shedding scheme can be made most effective if the shedding of load feeders is
distributed and discrete, that is, the loads are shed at various locations and in distinct steps
until the system frequency reaches the acceptable limits.
Due to the action of load-shedding schemes, the system recovers from the disturbance and
the operating frequency value recovers towards the nominal frequency. The load that was
shed during the disturbance can be restored. The load-restoring operation should be done
stepwise in such a way that it does not lead the system back to the emergency condition.
This is done through an operator intervention or in case of remote location through an
automatic load restoration function. The load restoration function also detects the system
frequency and restores the load if the system frequency remains above the value of the set
restoration frequency for a predefined duration.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......