1MAC309294-MB F
Section 6
Condition monitoring functions
RER620
371
Technical Manual
current is 10 kA, the operation counts from the curve at 10kA is about 60. One operation
at 10 kA will result in a reduction in the breaker life by 30,000/60=500 operations. If the
remaining life of the circuit breaker is 15,000 operations prior to this tripping, after one
operation of 10 kA, the remaining life of the circuit breaker is 15,000-500=14,500 at the
rated operating current. Breaker life reduction for one operation at current level I can also
be estimated by the following formula,
Remaining life reduction =
Spring charged indication
For normal operation of the circuit breaker, the circuit breaker spring should be charged
within a specified time. Therefore, detecting long spring charging time indicates that it is
time for the circuit breaker maintenance. The last value of the spring charging time can be
used as a service value.
Gas pressure supervision
The gas pressure supervision monitors the gas pressure inside the arc chamber. When the
pressure becomes too low compared to the required value, the circuit breaker operations
are locked. A binary input is available based on the pressure levels in the function, and
alarms are generated based on these inputs.
- Directional Coef
I
I
r
§
©
¨
·
¹
¸
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......