1MAC309294-MB F
Section 5
Control functions
RER620
317
Technical Manual
5.2.10
Settings
Table 299: 79 Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=On
5=Off
5=On
Operation mode Off/On. Setting this setting to “Off” will
prevent tripping by any protection function!
Reclosing operation
1=Off
2=External Ctl
3=On
1=On
Reclosing operation (Off, External Ctl / On)
Single phase mode
1=APAT
2=OPUP
3=OOAP
1=APAT
Mode of operation for the autorecloser in single-phase
mode
Shot mode 1
0...63
0
Defines 1P or 3P operation mode per input for first reclose
shot
Shot mode 2
0...63
0
Defines 1P or 3P operation mode per input for second
reclose shot
Shot mode 3
0...63
0
Defines 1P or 3P operation mode per input for third reclose
shot
Shot mode 4
0...63
0
Defines 1P or 3P operation mode per input for fourth
reclose shot
Shot mode 5
0...63
0
Defines 1P or 3P operation mode per input for fifth reclose
shot
Enable three-phase
lockout override
1=Disable
2=Enable
1=Disable
If enabled, performs a three-phase trip and lockout on the
last shot
Reclaim time
0.1...1800.0
s
0.1
10.0
Reclaim time
First reclose time
0.0...300.0
s
0.1
0.5
Reclose time for CBB1
Second reclose time
0.0...300.0
s
0.1
0.5
Reclose time for CBB2
Third reclose time
0.0...300.0
s
0.1
1.5
Reclose time for CBB3
Fourth reclose time
0.0...300.0
s
0.1
4.5
Reclose time for CBB4
Fifth reclose time
0.0...300.0
s
0.1
5.0
Reclose time for CBB5
Sixth reclose time
0.0...300.0
s
0.1
5.0
Reclose time for CBB6
Seventh reclose time
0.0...300.0
s
0.1
5.0
Reclose time for CBB7
Manual close mode
0=False
1=True
0=False
Manual close mode
Wait close time
0.05...10.00
s
0.01
0.25
Allowed CB closing time after reclose command
Max wait time
0.1...1800.0
s
0.1
10.0
Maximum wait time for BLK_RECL_T reclease (from
master)
Max trip time
0.1...10.0
s
0.1
10.0
Maximum wait time for protection signal deactivation
CB close pulse time
0.01...10.00
s
0.01
0.2
Close pulse time
Max thm block time
0.1...1800.0
s
0.1
10.0
Maximum wait time for thermal blocking deactivation
Cut-out time
0.1...1800.0
s
0.1
10.0
Protection coordination signal cut-out time
Dsr time shot 1
0.00...10.00
s
0.01
0.00
Discrimination time for first reclosing
Dsr time shot 2
0.00...10.00
s
0.01
0.00
Discrimination time for second reclosing
Dsr time shot 3
0.00...10.00
s
0.01
0.00
Discrimination time for third reclosing
Dsr time shot 4
0.00...10.00
s
0.01
0.00
Discrimination time for fourth reclosing
Terminal priority
1=None
2=Low (follower)
3=High (master)
1=None
Terminal priority
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......