1MAC309294-MB F
Section 3
Basic functions
RER620
47
Technical Manual
Table 30:
Internal fault indications and codes
Fault indication
Fault code Additional information
Internal Fault
System error
2
An internal system error has occurred.
Internal Fault
File system error
7
A file system error has occurred.
Internal Fault
Test
8
Internal fault test activated manually by the user.
Internal Fault
SW watchdog error
10
Watchdog reset has occurred too many times within an hour.
Internal fault
Supply voltage break
11
The auxiliary supply voltage has dropped to the failure level.
Internal fault
Settings error
32
Settings error has occurred.
Internal Fault
SO-relay(s),X105
40
Faulty Signal Output relay(s) in card located in slot X105.
Internal Fault
SO-relay(s),X115
41
Faulty Signal Output relay(s) in card located in slot X115.
Internal Fault
SO-relay(s),X100
43
Faulty Signal Output relay(s) in card located in slot X100.
Internal Fault
SO-relay(s),X110
44
Faulty Signal Output relay(s) in card located in slot X110.
Internal Fault
SO-relay(s),X120
45
Faulty Signal Output relay(s) in card located in slot X120.
Internal Fault
SO-relay(s),X130
46
Faulty Signal Output relay(s) in card located in slot X130.
Internal Fault
PO-relay(s),X105
50
Faulty Power Output relay(s) in card located in slot X105.
Internal Fault
PO-relay(s),X115
51
Faulty Power Output relay(s) in card located in slot X115.
Internal Fault
PO-relay(s),X100
53
Faulty Power Output relay(s) in card located in slot X100.
Internal Fault
PO-relay(s),X110
54
Faulty Power Output relay(s) in card located in slot X110.
Internal Fault
PO-relay(s),X120
55
Faulty Power Output relay(s) in card located in slot X120.
Internal Fault
PO-relay(s),X130
56
Faulty Power Output relay(s) in card located in slot X130.
Internal Fault
Light sensor error
57
Faulty ARC light sensor input(s).
Internal Fault
Conf. error,X105
60
Card in slot X105 is wrong type.
Internal Fault
Conf. error,X115
61
Card in slot X115 is wrong type.
Internal Fault
Conf. error,X000
62
Card in slot X000 is wrong type.
Internal Fault
Conf. error,X100
63
Card in slot X100 is wrong type or does not belong to the
original composition.
Internal Fault
Conf. error,X110
64
Card in slot X110 is wrong type, is missing or does not belong
to the original composition.
Internal Fault
Conf. error,X120
65
Card in slot X120 is wrong type, is missing or does not belong
to the original composition.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......