Section 4
1MAC309294-MB F
Protection functions
140
RER620
Technical Manual
For defining the operation sector, there are five modes available through the
Operation
mode
setting.
Table 162: Operation modes
The directional operation can be selected with the
Directional mode
setting. The user can
select either “Non-directional”, “Forward” or “Reverse” operation. The operation criterion
is selected with the
Operation mode
setting. By setting
Allow Non Dir
to “True”,
non-directional operation is allowed when directional information is invalid.
The
Characteristic angle
setting is used in “Phase angle” mode to adjust the operation
according to the method of neutral point earthing so that in an isolated network the
Characteristic angle
(φ
RCA
) = -90° and in a compensated network φ
RCA
= 0°. In addition,
the characteristic angle can be changed via the control signal
RCA_CTL
, in which case the
alternatives are -90° and 0°. The operation of
RCA_CTL
depends on the
Characteristic
angle
setting.
The
Correction angle
setting can be used to improve selectivity when there are
inaccuracies due to measurement transformers. The setting decreases the operation sector.
The correction can only be used with the “IoCos” or “IoSin” modes.
The minimum signal level which allows directional operation can be set by using the
Min
trip current
and
Min trip voltage
settings.
When polarizing quantity (residual voltage (-Uo)) is inverted because of switched voltage
measurement cables, the correction can be done by setting the
Pol reversal
to “True”
which turns polarizing quantity by 180 degrees.
The directional calculation module calculates several values which are presented in the
monitored data.
Operation mode
Description
Phase angle
The operating sectors for forward and reverse are
defined with the settings
Min forward angle
,
Max
forward angle
,
Min reverse angle
and
Max reverse
angle.
IoSin
The operating sectors are defined as “forward” when
the mathematical expression has a positive value
and “reverse” when the value is negative
IoCos
As “IoSin” mode. Only cosine is used for calculating
the operation current.
Phase angle 80
The sector maximum values are frozen to 80
degrees, respectively. Only Min forward angle and
Min reverse angle
are settable.
Phase angle 88
The sector maximum values are frozen to 88
degrees. Otherwise as “Phase angle 80” mode.
For definitions of different directional earth-fault characteristics, see the
Directional earth-fault characteristics section in this manual.
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......