1MAC309294-MB F
Section 10
General function block features
RER620
545
Technical Manual
protection
The user can define curves by entering parameters into the standard formula:
(Equation 67)
t[s]
trip time in seconds
A
the set value of
Curve parameter A
B
the set value of
Curve parameter B
C
the set value of
Curve parameter C
D
the set value of
Curve parameter D
E
the set value of
Curve parameter E
V
measured voltage
V<
the set value of
Pickup value
k
the set value of
Time multiplier
10.3.2.3
IDMT curve saturation of undervoltage protection
For the undervoltage IDMT mode of operation, the integration of the trip time does not
start until the voltage falls below the value of
Pickup value
. To cope with discontinuity
characteristics of the curve, a specific parameter for saturating the equation to a fixed value
is created. The
Curve Sat Relative
setting is the parameter and it is given in percents
compared with
Pickup value
. For example, due to the curve equation B, the characteristics
equation output is saturated in such a way that when input voltages are in the range from
Pickup value
to
Curve Sat Relative
in percents under
Pickup value
, the equation uses
Pickup value
* (1.0 -
Curve Sat Relative
/ 100) for the measured voltage. Although, the
curve A has no discontinuities when the ratio V/V> exceeds the unity,
Curve Sat Relative
is set for it as well. The
Curve Sat Relative
setting for curves A, B and C is 2.0 percent.
However, it should be noted that the user must carefully calculate the curve characteristics
concerning also discontinuities in the curve when the programmable curve equation is
used. Thus, the
Curve Sat Relative
parameter gives another degree of freedom to move the
inverse curve on the voltage ratio axis and it effectively sets the maximum trip time for the
IDMT curve because for the voltage ratio values affecting by this setting, the operation
time is fixed, that is, the definite time, depending on the parameters but no longer the
voltage.
10.4
Measurement modes
In many current or voltage dependent function blocks, there are four alternative measuring
principles:
• RMS
• DFT which is a numerically calculated fundamental component of the signal
• Peak-to-peak
• Peak-to-peak with peak backup
t s
k A
B
V
V
V
C
D
E
⎡
⎣⎢
⎤
⎦⎥
=
⋅
× < −
<
−
⎛
⎝⎜
⎞
⎠⎟
+
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......