1MAC309294-MB F
Section 5
Control functions
RER620
335
Technical Manual
Table 308: 25 non-group settings
5.3.8
Monitored data
Table 309: 25 monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Synch check mode
1=Off
2=Synchronous
3=Asynchronous
2=Synchronous
Synch check operation mode
Control mode
1=Continuous
2=Command
1=Continuous
Selection of synch check command or Continuous control
mode
Dead line value
0.1...0.8
xVn
0.1
0.2
Voltage low limit line for energizing check
Live line value
0.2...1.0
xVn
0.1
0.5
Voltage high limit line for energizing check
Dead bus value
0.1...0.8
xVn
0.1
0.2
Voltage low limit bus for energizing check
Live bus value
0.2...1.0
xVn
0.1
0.5
Voltage high limit bus for energizing check
Close pulse
200...60000
ms
10
200
Breaker closing pulse duration
Max energizing V
0.50...1.15
xVn
0.01
1.05
Maximum voltage for energizing
Phase shift
-180...180
deg
1
180
Correction of phase difference between measured V_BUS and
V_LINE
Minimum Syn time
0...60000
ms
10
0
Minimum time to accept synchronizing
Maximum Syn time
100...6000000
ms
10
2000
Maximum time to accept synchronizing
Energizing time
100...60000
ms
10
100
Time delay for energizing check
Closing time of CB
40...250
ms
10
60
Closing time of the breaker
Name
Type
Values (Range)
Unit
Description
ENERG_STATE
Enum
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
Energization state of Line and Bus
V_DIFF_MEAS
FLOAT32
0.00...1.00
xVn
Calculated voltage amplitude difference
FR_DIFF_MEAS
FLOAT32
0.000...0.100
xFn
Calculated voltage frequency difference
PH_DIFF_MEAS
FLOAT32
0.00...180.00
deg
Calculated voltage phase angle difference
V_DIFF_SYNC
BOOLEAN
0=False
1=True
Voltage difference out of limit for synchronizing
PH_DIF_SYNC
BOOLEAN
0=False
1=True
Phase angle difference out of limit for synchronizing
FR_DIFF_SYNC
BOOLEAN
0=False
1=True
Frequency difference out of limit for synchronizing
SECRSYN
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......