1MAC309294-MB F
Section 5
Control functions
RER620
301
Technical Manual
• The circuit breaker is closed manually during an autoreclose sequence and the manual
close mode is FALSE.
Protection coordination controller
The
PROT_CRD
output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses, tripping and
initiation of shot 1 should be fast (instantaneous or short-time delayed). The tripping and
initiation of shots 2, 3 and definite tripping time should be delayed.
In this example, two overcurrent elements 51P and 50P-2 are used. 50P-2 is given an
instantaneous characteristic and 51P is given a time delay.
The
PROT_CRD
output is activated, if the
SHOT_PTR
value is higher than the value
defined with the
Protection crd limit
setting and all initialization signals have been reset.
The
PROT_CRD
output is reset under the following conditions:
• If the cut-out time elapses
• If the reclaim time elapses and the AR function is ready for a new sequence
• If the AR function is in lockout or disabled, that is, if the value of the
Protection crd
mode
setting is
“
AR inoperative
”
or
“
AR inop, CB man
”
.
The
PROT_CRD
output can also be controlled with the
Protection crd mode
setting. The
setting has the following modes:
• “no condition”: the
PROT_CRD
output is controlled only with the
Protection crd limit
setting
• “AR inoperative”: the
PROT_CRD
output is active, if the AR function is disabled or
in the lockout state, or if the
INHIBIT_RECL
input is active
• “CB close manual”: the
PROT_CRD
output is active for the reclaim time if the circuit
breaker has been manually closed, that is, the AR function has not issued a close
command
• “AR inop, CB man”: both the modes “AR inoperative” and “CB close manual” are
effective
• “always”: the
PROT_CRD
output is constantly active
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......