ANSI09000887-3-en.vsdx
BLKTR
AND
AND
AND
PU_A
PU_B
PU_C
TRIP
TR_A
TR_B
TR_C
PUZMPP
tPP
AND
AND
PUZMPG
Timer tPG=enable
Timer tPP=enable
tPG
OR
AND
AND
AND
OR
OR
BLK
BLOCFUNC
0-tPP
0
0-tPG
0
0
15 ms
ANSI09000887 V3 EN-US
Figure 80: Tripping logic for the distance protection zone
7.1.8
Technical data
IP12804-1 v1
M13842-1 v15
Table 92: ZMQPDIS (21) Technical data
Function
Range or value
Accuracy
Number of zones
Max 5 with selectable
direction
-
Minimum trip residual current,
zone 1
(5-1000)% of IBase
-
Minimum trip current, phase-
to-phase and phase-to-
ground
(10-1000)% of IBase
-
Positive sequence reactance
(0.10-3000.00) Ω/phase
±2.0% static accuracy
±2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Angle: at 0 degrees and 85 degrees
Positive sequence resistance
(0.01-1000.00) Ω/phase
Zero sequence reactance
(0.10-9000.00) Ω/phase
Zero sequence resistance
(0.01-3000.00) Ω/phase
Fault resistance, phase-to-
ground
(0.10-9000.00) Ω/loop
phase-to-phase
(0.10-3000.00) Ω/loop
Table continues on next page
Section 7
1MRK 502 066-UUS B
Impedance protection
196
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...