Name
Type
Values (Range)
Unit
Description
BO10VALUE
BOOLEAN
1=1
0=0
-
Binary output 10 value
BO10FORCE
BOOLEAN
0=Normal
1=Forced
-
Binary output 10 force
BO10
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 10 status
BO11VALUE
BOOLEAN
1=1
0=0
-
Binary output 11 value
BO11FORCE
BOOLEAN
0=Normal
1=Forced
-
Binary output 11 force
BO11
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 11 status
BO12VALUE
BOOLEAN
1=1
0=0
-
Binary output 12 value
BO12FORCE
BOOLEAN
0=Normal
1=Forced
-
Binary output 12 force
BO12
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 12 status
22.2.9.6
Technical data
SEMOD175396-1 v1
SEMOD175395-2 v9
Table
1020:
SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Static binary output trip
Rated voltage
48-60 VDC
110-250 VDC
Number of outputs
6
6
Impedance open state
~300 kΩ
~810 kΩ
Test voltage across open contact, 1
min
No galvanic separation
No galvanic separation
Current carrying capacity:
Continuous
5 A
5 A
1.0 s
10 A
10 A
Making capacity at capacitive load with
the maximum capacitance of 0.2 μF :
0.2 s
30 A
30 A
1.0 s
10 A
10 A
Breaking capacity for DC with L/R ≤ 40
ms
48 V/1 A
110 V/0.4 A
60 V/0.75 A
125 V/0.35 A
Table continues on next page
1MRK 502 066-UUS B
Section 22
IED hardware
1305
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...