Name
Values (Range)
Unit
Step
Default
Description
R1FwPPZ3
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-Ph, zone 3,
zone direction
RFFwPPZ3
0.01 - 9000.00
Ohm/l
0.01
30.00
Positive seq. resistive reach, Ph-Ph, zone 3,
zone direction
X1RvPPZ3
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-Ph, zone 3,
opposite to zone dir
RFRvPPZ3
0.01 - 9000.00
Ohm/l
0.01
30.00
Positive seq. resistive reach, Ph-Ph, zone 3,
zone direction
X1FwPGZ3
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. resistive reach, Ph-G, zone 3,
zone direction
R1FwPGZ3
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-G, zone 3,
zone direction
X0FwPGZ3
0.01 - 9000.00
Ohm/p
0.01
120.00
Zero seq. reactance reach, Ph-G, zone 3,
zone direction
R0FwPGZ3
0.01 - 3000.00
Ohm/p
0.01
15.00
Zero seq. resistive reach, Ph-G, zone 3,
zone direction
RFFwPGZ3
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-G, zone 3, zone
direction
X1RvPGZ3
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-G, zone 3,
opposite to zone dir
RFRvPGZ3
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-G, zone 3,
opposite to zone dir.
tPPZ3
0.000 - 60.000
s
0.001
0.800
Time delay to trip, Phase-Phase, zone 3
tPGZ3
0.000 - 60.000
s
0.001
0.800
Time delay to trip, Phase-Ground, zone 3
IMinOpPPZ3
10 - 6000
%IB
1
10
Minimum operate ph-ph current for Phase-
Phase loops, zone 3
IMinOpPGZ3
5 - 6000
%IB
1
10
Minimum operate phase current for phase-
ground loops, zone 3
OpModePPZ4
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 4
OpModePGZ4
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 4
DirModeZ4
Non-directional
Forward
Reverse
-
-
Forward
Direction of zone 4 (which will be the Fw
direction of zone 4)
X1FwPPZ4
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. reactance reach, Ph-Ph, zone
4, zone direction
R1FwPPZ4
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-Ph, zone 4,
zone direction
RFFwPPZ4
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone 4, zone
direction
X1RvPPZ4
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-Ph, zone 4,
opposite to zone dir
RFRvPPZ4
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone 4,
opposite to zone dir.
Table continues on next page
1MRK 502 066-UUS B
Section 7
Impedance protection
335
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...