Name
Values (Range)
Unit
Step
Default
Description
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Selection of time delay curve type for step
1
Pickup1
5 - 2500
%IB
1
1000
Operating phase current level for step 1 in
% of IBase
t1
0.000 - 60.000
s
0.001
0.000
Def time delay or add time delay for
inverse char of step 1
TD1
0.05 - 999.00
-
0.01
0.05
Time dial multiplier for the inverse time
delay for step 1
IMin1
1 - 10000
%IB
1
100
Minimum operate current for step1 in % of
IBase
t1Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse curves
for step 1
MultPU1
1.0 - 10.0
-
0.1
2.0
Multiplier for current operate level for step
1
DirModeSel2
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (Disabled,
Nondir, Forward, Reverse)
Characterist2
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Selection of time delay curve type for step
2
Pickup2
5 - 2500
%IB
1
500
Operating phase current level for step 2 in
% of IBase
Table continues on next page
Section 8
1MRK 502 066-UUS B
Current protection
454
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...