activating of the input
BLKHSIR
blocks the high speed part of the algorithm for high SIR
values
•
activating of the input
BLKTRIP
blocks all output signals
•
activating the input
BLKPG
blocks the phase-to-ground fault loop outputs
•
activating the input
BLKPP
blocks the phase-to-phase fault loop outputs
The activation of input signal
BLKZ
can be made by external fuse failure function or from the loss
of voltage check in the Mho supervision logic (ZSMGAPC). In both cases the output
BLKZ
in the
Mho supervision logic shall be connected to the input
BLKZ
in the Mho distance function block
(ZMHPDIS, 21)
The input signal
BLKZMTD
is activated during some ms after fault has been detected by ZSMGAPC
to avoid unwanted operations due to transients. It shall be connected to the
BLKZMTD
output
signal of ZSMGAPC function.
At SIR values >10, the use of electronic CVT might cause overreach due to the built-in resonance
circuit in the CVT, which reduce the secondary voltage for a while. The input
BLKHSIR
is connected
to the output signal
HSIR
on ZSMGAPC for increasing of the filtering and high SIR values. This is
valid only when permissive underreach scheme is selected by setting
ReachMode=Underreach.
7.3.6.4
Theory of operation
SEMOD154224-46 v6
The mho algorithm is based on the phase comparison of an operating phasor and a polarizing
phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or more,
the function operates and gives a trip output.
Phase-to-phase fault
SEMOD154224-240 v2
Mho
SEMOD154224-217 v5
The plain Mho circle has the characteristic as in Figure
. The condition for deriving the angle β is
according to equation
(
)
( )
AB
AB
pol
ang V
I
ZPP
ang V
b =
-
×
-
EQUATION1789-ANSI V1 EN-US
(Equation 55)
where
AB
V
EQUATION1790-ANSI
V1 EN-US
is the voltage vector difference between phases A and B
AB
I
EQUATION1791-ANSI
V1 EN-US
is the current vector difference between phases A and B
ZPP
is the positive sequence impedance setting for phase-to-phase fault
V
pol
is the polarizing voltage
The polarized voltage consists of 100% memorized positive sequence voltage (VAB for phase A to
B fault). The memorized voltage will prevent collapse of the Mho circle for close in faults.
Operation occurs if 90≤β≤270
Section 7
1MRK 502 066-UUS B
Impedance protection
222
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...