Name
Type
Description
SLIPZPER
REAL
Slip impedance in percent of ZBase
VCOS
REAL
UCosPhi voltage
VCOSPER
REAL
VCosPhi voltage in percent of VBase
7.10.5
Settings
PID-3526-SETTINGS v3
Table 158: PSPPPAM (78) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Enable / Disable
OperationZ1
Disabled
Enabled
-
-
Enabled
Operation Enable/Disable zone Z1
OperationZ2
Disabled
Enabled
-
-
Enabled
Operation Enable/Disable zone Z2
ImpedanceZA
0.00 - 1000.00
%
0.01
10.00
Forward impedance in % of Zbase
ImpedanceZB
0.00 - 1000.00
%
0.01
10.00
Reverse impedance in % of Zbase
ImpedanceZC
0.00 - 1000.00
%
0.01
10.00
Impedance of zone1 limit in % of Zbase
AnglePhi
72.00 - 90.00
Deg
0.01
85.00
Angle of the slip impedance line
pick up Angle
0.0 - 180.0
Deg
0.1
110.0
Rotor angle for the pickup signal
TripAngle
0.0 - 180.0
Deg
0.1
90.0
Rotor angle for the trip1 and trip2 signals
N1Limit
1 - 20
-
1
1
Count limit for the trip1 signal
N2Limit
1 - 20
-
1
3
Count limit for the trip2 signal
Table 159: PSPPPAM (78) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
ResetTime
0.000 - 60.000
s
0.001
5.000
Time without slip to reset all signals
Table 160: PSPPPAM (78) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
MeasureMode
PosSeq
AB
BC
CA
-
-
PosSeq
Measuring mode (PosSeq, AB, BC, CA)
InvertCTcurr
No
Yes
-
-
No
Invert current direction
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Section 7
1MRK 502 066-UUS B
Impedance protection
370
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...