The output signals can be of the types Disabled, Steady, or Pulse. This configuration setting is
done via the local HMI or PCM600 and is common for the whole function block. The length of the
output pulses are 100 ms. In steady mode, SINGLECMD function has a memory to remember the
output values at power interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in functions or via the
configuration logic circuits to the binary outputs of the IED.
Section 14
1MRK 502 066-UUS B
Control
936
Technical manual