that the cross block signals from the other two phases B and C is not activated to obtain a
trip on the TRIPRES_A output signal in figure
)
6. All pickup and blocking conditions are available as phase segregated as well as common (that
is three-phase) signals.
ANSI06000546-2-en.vsd
&
IDiffAlarm
a
a>b
b
IDMAG_C Diff
IDiffAlarm
a
a>b
b
IDMAG_B Diff
IDiffAlarm
a
a>b
b
IDMAG_A Diff
IDALARM
0
0-tAlarmDelay
ANSI06000546 V2 EN-US
Figure 46: Differential current alarm logic
6.1.8
Technical data
IP12646-1 v1
M13046-1 v14
Table 58: T2WPDIF/T3WPDIF (87T) technical data
Function
Range or value
Accuracy
Operating characteristic
Adaptable
±1.0% of In at I ≤ In
±1.0% of I at I > In
Reset ratio
> 90%
-
Unrestrained differential current
limit
(100-5000)% of
IBase on high
voltage winding
±1.0% of set value
Minimum pickup
(10-60)% of IBase
±1.0% of In
Second harmonic blocking
(5.0-100.0)% of fundamental
differential current
±1.0% of I
n
Note: Fundamental magnitude =
100% of I
n
Fifth harmonic blocking
(5.0-100.0)% of fundamental
differential current
±5.0% of I
n
Note: Fundamental magnitude =
100% of I
n
Connection type for each of the
windings
Wye or delta
-
Phase displacement between high
voltage winding, W1 and each of the
windings, W2 and W3. Hour notation
0–11
-
*Trip time at 0 to 10 x IdMin,
restrained function
Min. = 25 ms
Max. = 35 ms
-
*Reset time at 10 x IdMin to 0,
restrained function
Min. = 5 ms
Max. = 15 ms
-
Table continues on next page
1MRK 502 066-UUS B
Section 6
Differential protection
143
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...