Cause
number
Name
Description
Supported
14
1-of-n-control
Control action is blocked because another control action in a
domain (for example, substation) is already running (in any
XCBR or XSWI of that domain, the DPC.stSeld=”TRUE”)
X
15
Abortion-by-cancel
Control action is aborted due to cancel service
X
16
Time-limit-over
Control action is terminated due to exceed of some time limit
X
17
Abortion-by-trip
Control action is aborted due to a trip (PTRC with
ACT.general=”TRUE”)
X
18
Object-not-selected
Control action is rejected, because control object was not
selected
X
19
Object-already-
selected
Select action is not executed because the addressed object is
already selected
X
20
No-access-authority
Control action is blocked due to lack of access authority
X
21
Ended-with-overshoot
Control action executed but the end position has overshoot
22
Abortion-due-to-
deviation
Control action is aborted due to deviation between the
command value and the measured value
23
Abortion-by-
communication-loss
Control action is aborted due to the loss of connection with
the client that issued the control
24
Blocked-by-command
Control action is blocked due to the data attribute
CmdBlk.stVal is TRUE
X
26
Inconsistent-
parameters
The parameters between successive control services are not
consistent, for example the ctlNum of Select and Operate
service are different
X
27
Locked-by-other-client
Another client has already reserved the object
X
-22
Wrong-Ctl-model
Command from client uses wrong control model
X
-23
Blocked-by-command
Blocked by command
X
-24
Blocked-for-open-cmd
Blocked for Open command
X
-25
Blocked-for-close-cmd
Blocked for Close Command
X
-30
Long-operation-time
Operation time too long
X
-31
Switch-not-start-
moving
Switch did not start moving
X
-32
Persistent-
intermediate-state
Switch stopped in intermediate state
X
-33
Switch-returned-to-
init-pos
Switch returned to the initial position
X
-34
Switch-in-bad-state
Switch is in a bad position state
X
-35
Not-expected-final-
position
Switch did not reach the expected final position
X
Section 14
1MRK 502 066-UUS B
Control
828
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...