Name of signal
Description
Displayed on
local HMI as
Reasons for activation
TIMESYNCHERROR
Time
Synchronizat
ion status
Time synch
This signal will be active when the source of the time
synchronization is lost, or when the time system has to
make a time reset.
RTEERROR
Runtime
Execution
Error status
Runtime
execution
This signal will be active if the Runtime Engine failed to
do some actions with the application threads. The
actions can be loading of settings or parameters for
components, changing of setting groups, loading or
unloading of application threads.
IEC61850ERROR
IEC 61850
Error status
IEC61850
This signal will be active if the IEC 61850 stack did not
succeed in some actions like reading IEC 61850
configuration, startup, for example
DNP3
DNP3 error
status
DNP3
This signal will be active when DNP3 detects any
configuration error during startup.
LMDERROR
LON/Mip
Device Error
status
SLM301
LON network interface, MIP/DPS, is in an unrecoverable
error state.
APPERROR
Runtime
Application
Error status
Runtime App
Error
This signal will be active if one or more of the application
threads are not in the state that Runtime Engine expects.
The states can be CREATED, INITIALIZED, RUNNING, for
example
SETCHGD
Settings
changed
Settings
changed
This signal will generate an Internal Event to the Internal
Event list if any settings are changed.
SETGRPCHGD
Setting
groups
changed
Settings
changed
This signal will generate an Internal Event to the Internal
Event list if any setting groups are changed.
Table 950: Self-supervision's hardware dependent internal signals
Card
Name of signal
Description
Displayed on
local HMI as
Reasons for activation
PSM
PSM-Error
Power
Supply
Module Error
status
PSM1
Activated if the module has a hardware error.
BIM
BIM-Error
Binary In
Module Error
status
BIMn
Activated if the module has a hardware error.
n = slot number
BOM
BOM-Error
Binary Out
Module Error
status
BOMn
Activated if the module has a hardware error.
n = slot number
IOM
IOM-Error
In/Out
Module Error
status
IOMn
Activated if the module has a hardware error.
n = slot number
MIM
MIM-Error
Millampere
Input Module
Error status
MIMn
Activated if the module has a hardware error.
n = slot number
SOM
SOM-Error
Static Out
Module Error
status
SOMn
Activated if the module has a hardware error.
n = slot number
NUM
NUM-Error
Numerical/C
PU Module
Error status
NUM30
Activated if the module has a hardware or
software error.
Table continues on next page
Section 20
1MRK 502 066-UUS B
Security
1230
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...