Function
Range or value
Accuracy
Time delay for pressure alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Reset time delay for pressure alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for pressure lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Reset time delay for temperature
alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for temperature lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
16.3
Liquid medium supervision SSIML (71)
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
16.3.1
Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Liquid medium supervision
SSIML
-
71
16.3.2
Functionality
GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v5
Liquid medium supervision SSIML (71) is used for monitoring the circuit breaker condition. Binary
information based on the oil level in the circuit breaker is used as input signals to the function. In
addition, the function generates alarms based on received information.
16.3.3
Function block
GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3
ANSI09000128-1-en.vsd
SSIML (71)
BLOCK
BLK_ALM
LEVEL
TEMP
LVL_ALM
LEVEL_LO
SET_L_LO
SET_T_LO
RESET_LO
LEVEL
LVL_ALM
LVL_LO
TEMP
TEMP_ALM
TEMP_LO
ANSI09000128 V1 EN-US
Figure 542: SSIML (71) function block
16.3.4
Signals
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v2
1MRK 502 066-UUS B
Section 16
Monitoring
1045
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...