18.8.13.3
Function block
GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1
IEC10000285-1-en.vsd
I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285 V1 EN-US
Figure 605: I103GENCMD function block
18.8.13.4
Signals
PID-3970-INPUTSIGNALS v4
Table 885: I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
PID-3970-OUTPUTSIGNALS v4
Table 886: I103GENCMD Output signals
Name
Type
Description
CMD_OFF
BOOLEAN
Command output OFF
CMD_ON
BOOLEAN
Command output ON
18.8.13.5
Settings
PID-3970-SETTINGS v4
Table 887: I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
1 - 255
-
1
1
Information number for command output
(1-255)
18.8.14
IED commands with position and select for IEC 60870-5-103
I103POSCMD
18.8.14.1
Functionality
GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v8
I103POSCMD is a transceiver function that monitors activity on its input signals and interprets any
state transition into commands then sent over an established IEC 60870-5-103 link. Additionally, it
listens for general interrogation (GI) requests and replies to those with a GI response message
with the current state of each connected input.
Input POSITION is a double-indication signal, and it is GI enabled. This means that any state
transition, that is to ON, OFF, intermediate and faulty, is reported spontaneously. However, the
1MRK 502 066-UUS B
Section 18
Station communication
1179
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...