Name
Values (Range)
Unit
Step
Default
Description
IntBlkStVal2
1 - 50
%VB
1
20
Voltage setting for internal blocking in %
of VBase, step 2
tBlkUV2
0.000 - 60.000
s
0.001
0.000
Time delay of internal (low level) blocking
for step 2
HystAbs2
0.0 - 50.0
%VB
0.1
0.5
Absolute hysteresis in % of VBase, step 2
Table 336: UV2PTUV (27) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tReset1
0.000 - 60.000
s
0.001
0.025
Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1
Instantaneous
Frozen timer
Linearly
decreased
-
-
Instantaneous
Selection of used IDMT reset curve type for
step 1
tIReset1
0.000 - 60.000
s
0.001
0.025
Time delay in Inverse-Time reset (s), step 1
ACrv1
0.005 - 200.000
-
0.001
1.000
Parameter A for customer programmable
curve for step 1
BCrv1
0.50 - 100.00
-
0.01
1.00
Parameter B for customer programmable
curve for step 1
CCrv1
0.0 - 1.0
-
0.1
0.0
Parameter C for customer programmable
curve for step 1
DCrv1
0.000 - 60.000
-
0.001
0.000
Parameter D for customer programmable
curve for step 1
PCrv1
0.000 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 1
CrvSat1
0 - 100
%
1
0
Tuning param for prog. under voltage
Inverse-Time curve, step 1
tReset2
0.000 - 60.000
s
0.001
0.025
Reset time delay used in IEC Definite Time
curve step 2
ResetTypeCrv2
Instantaneous
Frozen timer
Linearly
decreased
-
-
Instantaneous
Selection of Time Delay reset curve for
step 2
tIReset2
0.000 - 60.000
s
0.001
0.025
Time delay in Inverse-Time reset (s), step 2
ACrv2
0.005 - 200.000
-
0.001
1.000
Parameter A for customer programmable
curve for step 2
BCrv2
0.50 - 100.00
-
0.01
1.00
Parameter B for customer programmable
curve for step 2
CCrv2
0.0 - 1.0
-
0.1
0.0
Parameter C for customer programmable
curve for step 2
DCrv2
0.000 - 60.000
-
0.001
0.000
Parameter D for customer programmable
curve for step 2
PCrv2
0.000 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 2
CrvSat2
0 - 100
%
1
0
Tuning param for prog. under voltage
Inverse-Time curve, step 2
Section 9
1MRK 502 066-UUS B
Voltage protection
602
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...