0
200
400
600
800
1000
1200
1400
-4
-3
-2
-1
0
1
2
3
4
Time in millis econds
®
Im
pe
da
nc
e
Z
in
O
hm
a
nd
r
ot
or
a
ng
le
in
r
ad
ia
n
®
|Z| in Ohms
angle in rad
normal
load
fault 500 ms
Z(R,X) cros s e d
the im pe da nce line , Z-line ,
conne cting points S E - RE
fault
occurrs
Z(R, X) under fault lies
on the impedance line
or near (for 3-ph faults )
Unde r 3-pha s e fa ult
condition rotor a ngle
of a pp. ±180 de gre e s
is m e a s ure d ...
rotor (power)
angle
|Z|
IEC10000110-2-en.vsd
1
2
3
1
0
IEC10000110 V2 EN-US
Figure 201: Rotor (power) angle and magnitude of the complex impedance Z(R, X) against the
time
In order to be able to fully understand the principles of OOSPPAM (78), a stable case, that is, a case
where the disturbance does not make a generator to go out-of-step, must be shown.
Section 7
1MRK 502 066-UUS B
Impedance protection
380
Technical manual
Содержание Relion 670 series