22.2
Hardware modules
IP14529-1 v1
22.2.1
Overview
M11562-3 v7
Table
1000:
Basic modules
Module
Description
Power supply module (PSM)
Including a regulated DC/DC converter that supplies auxiliary
voltage to all static circuits.
•
An internal fail alarm output is available.
Numerical module (NUM)
Module for overall application control. All information is
processed or passed through this module, such as configuration,
settings and communication.
Local Human machine interface (LHMI)
The module consists of LED:s, an LCD, a push button keyboard
and an ethernet connector used to connect a PC to the IED.
Transformer input module (TRM)
Transformer module that galvanically separates the internal
circuits from the VT and CT circuits. It has 12 analog inputs.
Analog digital conversion module (ADM)
Slot mounted PCB with A/D conversion.
Table 1001:Application specific modules
Module
Description
Binary input module (BIM)
Module with 16 optically isolated binary inputs
Binary output module (BOM)
Module with 24 single outputs or 12 double-pole command
outputs including supervision function
Binary I/O module (IOM)
Module with 8 optically isolated binary inputs, 10 outputs and 2
fast signalling outputs.
Line data communication modules (LDCM),
short range, medium range ,long range,X21
Modules used for digital communication to remote terminal.
Serial SPA/LON/IEC 60870-5-103
communication modules (SLM)
Used for SPA/LON/IEC 60870–5–103 communication
Optical ethernet module (OEM)
PMC board for IEC 61850 based communication.
mA input module (MIM)
Analog input module with 6 independent, galvanically separated
channels.
GPS time synchronization module (GSM)
Used to provide the IED with GPS time synchronization.
IRIG-B Time synchronization module (IRIG-B)
Module with 2 inputs. One is used for handling both pulse-width
modulated signals and amplitude modulated signals and one is
used for optical input type ST for PPS time synchronization.
22.2.2
Numeric processing module (NUM)
IP14288-1 v1
22.2.2.1
Introduction
M12643-3 v1
The Numeric processing module (NUM), is a CPU-module that handles all protection functions and
logic.
Section 22
1MRK 502 066-UUS B
IED hardware
1280
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...