PID-3630-OUTPUTSIGNALS v4
Table 507: RESIN2 Output signals
Name
Type
Description
ACK_F_B
BOOLEAN
All other bays have acknowledged the reservation request from
this bay
ANY_ACK
BOOLEAN
Any other bay has acknowledged the reservation request from
this bay
VALID_TX
BOOLEAN
The reservation and acknowledge signals from other bays are
valid
RE_RQ_B
BOOLEAN
Request from other bay to reserve this bay
V_RE_RQ
BOOLEAN
Check if the request of reserving this bay is valid
EXCH_OUT
INTEGER
Used for exchange signals between different ResIn blocks
14.3.11.4
Settings
PID-3629-SETTINGS v4
Table 508: RESIN1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FutureUse
Bay in use
Bay future use
-
-
Bay in use
The bay for this ResIn block is for future
use
PID-3630-SETTINGS v4
Table 509: RESIN2 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FutureUse
Bay in use
Bay future use
-
-
Bay in use
The bay for this ResIn block is for future
use
14.3.11.5
Operation principle
M16503-3 v6
The reservation input (RESIN) function is based purely on Boolean logic conditions. The logic
shows how the output signals are created. The inputs of the function block
are connected to a receive function block representing signals transferred over the station bus
from another bay.
Section 14
1MRK 502 066-UUS B
Control
866
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...