PID-3816-INPUTSIGNALS v4
Table 677: TIMERSETQT Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
PID-3816-OUTPUTSIGNALS v4
Table 678: TIMERSETQT Output signals
Name
Type
Description
ON
BOOLEAN
Output signal, pick-up delayed
OFF
BOOLEAN
Output signal, drop-out delayed
15.7.10.3
Settings
PID-3816-SETTINGS v4
Table 679: TIMERSETQT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
t
0.000 -
90000.000
s
0.001
0.000
Delay for settable timer n
15.7.10.4
Technical data
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
Table 680: Number of TIMERSETQT instances
Logic block
Quantity with cycle time
Range or Value
Accuracy
3 ms
8 ms
100 ms
TIMERSETQT
-
10
30
(0.000–90000.000) s
±0.5% ±10 ms
15.7.11
Exclusive OR function block XORQT
GUID-76ADACC1-A273-4100-BE62-99BCDABFEB7A v2
GUID-62986D87-1690-499E-B8D3-1F51D2DA191E v3
The exclusive OR function (XORQT) function is used to generate combinatory expressions with
boolean variables. XORQT function has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they are equal.
Table 681: Truth table for XORQT function block
INPUT1
INPUT2
OUT
NOUT
0
0
0
1
0
1
1
0
1
0
1
0
1
1
0
1
Section 15
1MRK 502 066-UUS B
Logic
980
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...