There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicate three
states with the colors: green, yellow and red. The texts related to each three-color LED are divided
into three panels.
There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one LED group
can indicate 45 different signals. Altogether, 135 signals can be indicated since there are three LED
groups. The LEDs are lit according to priority, with red being the highest and green the lowest
priority. For example, if on one panel there is an indication that requires the green LED to be lit,
and on another panel there is an indication that requires the red LED to be lit, the red LED takes
priority and is lit. The LEDs can be configured with PCM600 and the operation mode can be
selected with the LHMI or PCM600.
Information panels for the indication LEDs are shown by pressing the Multipage button. Pressing
that button cycles through the three pages. A lit or un-acknowledged LED is indicated with a
highlight. Such lines can be selected by using the Up/Down arrow buttons. Pressing the Enter key
shows details about the selected LED. Pressing the ESC button exits from information pop-ups as
well as from the LED panel as such.
The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit. If there are un-
acknowledged indication LEDs, then the Multipage LED blinks. To acknowledge LEDs, press the
Clear button to enter the Reset menu (refer to description of this menu for details).
There are two additional LEDs which are next to the control buttons
and
. They can, for
example, represent the status of a circuit breaker. The LEDs are controlled by the function block
OPENCLOSE_LED which must be configured to show the status of the breaker.
5.5.2
LED configuration alternatives
5.5.2.1
Functionality
GUID-1A03E0EF-C10F-4797-9D9F-5CCA86CA29EB v5
The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx (x=1-15) controls and
supplies information about the status of the indication LEDs. The input and output signals of the
function blocks are configured with PCM600. The input signal for each LED is selected individually
using SMT or ACT. Each LED is controlled by the GRPn_LEDx (n=1-3) function block that controls
the color and the operating mode.
Each indication LED on local HMI can be set individually to operate in 6 different sequences; two as
follow type and four as latch type. Two of the latching sequence types are intended to be used as a
protection indication system, either in collecting or restarting mode, with reset functionality. The
other two are intended to be used as signalling system in collecting mode with acknowledgment
functionality.
5.5.2.2
Status LEDs
GUID-4822DF9C-E343-442B-B3F1-3FA8CD8DF234 v4
There are three status LEDs above the LCD in front of the IED: green, yellow and red.
The green LED has a fixed function that presents the healthy status of the IED. The yellow and red
LEDs are user configured. The yellow LED can be used to indicate that a disturbance report is
triggered (steady) or that the IED is in test mode (flashing). The red LED can be used to indicate a
trip command.
Here is a typical configuration of the status LEDs:
Section 5
1MRK 502 066-UUS B
Local Human-Machine-Interface LHMI
94
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...