Name
Values (Range)
Unit
Step
Default
Description
tPEZRV
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase -Ground, zone RV
IMinOpPPZRV
10 - 6000
%IB
1
10
Minimum operate ph-ph current for Phase-
Phase loops, zone RV
IMinOpPGZRV
5 - 6000
%IB
1
10
Minimum operate phase current for phase-
ground loops, zone RV
X1ZRV
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive sequence reactance reach, zone
RV
R1ZRV
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive sequence resistive reach, zone RV
X0ZRV
0.01 - 9000.00
Ohm/p
0.01
120.00
Zero sequence reactance reach, zone RV
R0ZRV
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero sequence resistive reach, zone RV
RFPPZRV
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone RV
RFPGZRV
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach Ph-G. zone RV
Table 143: ZMFPDIS (21) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
ZoneLinkPU
Phase Selection
1st starting zone
-
-
Phase Selection
Select. of start source for all ZoneLinked
trip delay timers
3I0Enable_PG
5 - 400
%MaxIP
h
1
400
3I0 limit for releasing Phase-to-Ground
measuring loops
TimerModeZ1
Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH
-
-
Enable Ph-G
PhPH
On/Off setting for Ph-Ph and Ph-G trip
output, zone 1
TimerLinksZ1
LoopLink (tPP &
tPG)
LoopLink &
ZoneLink
no links
-
-
LoopLink (tPP &
tPG)
How start of trip delay timers should be
linked for zone 1
TimerModeZ2
Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH
-
-
Enable Ph-G
PhPH
On/off setting for Ph-Ph and Ph-G trip
output, zone 2
TimerLinksZ2
LoopLink (tPP &
tPG)
LoopLink &
ZoneLink
no links
-
-
LoopLink (tPP &
tPG)
How start of trip delay timers should be
linked for zone 2
TimerModeZ3
Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH
-
-
Enable Ph-G
PhPH
On/off setting for Ph-Ph and Ph-G trip
output, Zone 3
TimerLinksZ3
LoopLink (tPP &
tPG)
LoopLink &
ZoneLink
no links
-
-
LoopLink (tPP &
tPG)
How start of trip delay timers should be
linked for zone 3
TimerLinksZ4
Disable all
Enable Ph-G
Enable PhPh
Enable Ph-G PhPH
-
-
Enable Ph-G
PhPH
On/off setting for Ph-Ph and Ph-G trip
output Zone 4
Table continues on next page
1MRK 502 066-UUS B
Section 7
Impedance protection
299
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...