16.10.4
Signals
PID-6998-INPUTSIGNALS v1
Table 794: TEILGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the accumulation and block the outputs
IN
BOOLEAN
0
The input signal that is used to measure the elapsed time, when
its value is high
ADDTIME
BOOLEAN
0
Add time to the accumulation
RESET
BOOLEAN
0
Reset accumulated time
PID-6998-OUTPUTSIGNALS v1
Table 795: TEILGAPC Output signals
Name
Type
Description
ALARM
BOOLEAN
Indicator that accumulated time has reached alarm limit
WARNING
BOOLEAN
Indicator that accumulated time has reached warning limit
OVERFLOW
BOOLEAN
Indicator that accumulated time has reached overflow limit
ACC_HOUR
REAL
Accumulated time in hours
ACC_DAY
REAL
Accumulated time in days
16.10.5
Settings
PID-6998-SETTINGS v1
Table 796: TEILGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
tAlarm
1.0 - 99999.9
Hour
0.1
90000.0
Time limit for alarm supervision
tWarning
1.0 - 99999.9
Hour
0.1
50000.0
Time limit for warning supervision
tAddToTime
0.0 - 99999.9
Hour
0.1
0.0
Time to add to the accumulation
16.10.6
Operation principle
GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3
Figure
describes the simplified logic of the function.
Section 16
1MRK 502 066-UUS B
Monitoring
1098
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...