Name
Type
Description
PU_Z1
BOOLEAN
Pick up of any phase or phases from a Zone 1 fault in the forward
direction
PU_ND_Z1
BOOLEAN
Pick up any phase or phases from zone 1 - any direction
PU_Z2
BOOLEAN
Pick up of any phase or phases from a Zone 2 fault in the forward
direction
PU_A_Z2
BOOLEAN
Pick up of phase A for a zone 2 fault in forward direction
PU_B_Z2
BOOLEAN
Pick up for phase B fault in forward direction
PU_C_Z2
BOOLEAN
Pick up in phase C for a zone 2 fault in the forward direction
PU_ND_Z2
BOOLEAN
Pick uo in any phase or phases for a zone 2 fault in any direction
PU_Z3
BOOLEAN
Pick up of any phase or phases from a Zone 3 fault in the forward
direction
PU_ND_Z3
BOOLEAN
Pick up any phase or phases from zone 3- any direction
PU_Z4
BOOLEAN
Pick up in any pjase or phases for a zone 4 fault - zone direction
PU_ND_Z4
BOOLEAN
Pick up any phase or phases from zone -4 any direction
PU_Z5
BOOLEAN
Pick up in any phase or phase for Zone 5 - Zone direction
STND_Z5
BOOLEAN
Pick up in any phase or phases from a zone 5 fault in any direction
PU_ZRV
BOOLEAN
Pick up in any phase or phase for a reverse fault
PU_A_RV
BOOLEAN
Pick up for a phase A reverse fault
PU_B_RV
BOOLEAN
Pick up for a phase B revers fault
PU_C_RV
BOOLEAN
Pick up for a phase C reverse fault
STNDRV
BOOLEAN
Pick up for a reverse zone for a fauult in nay direction
PHPUND
BOOLEAN
Fault detected in any phase or phases - any direction
NDIR_A
BOOLEAN
Fault detected in phase A - any direction
NDIR_B
BOOLEAN
Fault detected in phase B - any direction
NDIR_C
BOOLEAN
Fault detected in phase C - any direction
FWD_A
BOOLEAN
Fault detected in phaseA - forward direction
FWD_B
BOOLEAN
Fault detected in phase B - forward direction
FWD_C
BOOLEAN
Fault detected in phase C - forward direction
FWD_G
BOOLEAN
forward fault involving ground
REV_A
BOOLEAN
Fault detected in phase A- reverse direction
REV_B
BOOLEAN
Fault detected in phase B - reverse direction
REV_C
BOOLEAN
Fault detected in phase C - reverse direction
REV_G
BOOLEAN
Fault in reverse direction involving ground
FWD_1PH
BOOLEAN
Single-phase fault detected - forward direction
FWD_2PH
BOOLEAN
Two-phase fault detected - forward direction
FWD_3PH
BOOLEAN
Three-phase fault detected - forward direction
PHG_FLT
BOOLEAN
Ph-G zone measurement enabled - any direction
PHPH_FLT
BOOLEAN
Ph-Ph zone measurement enabled - any direction
Section 7
1MRK 502 066-UUS B
Impedance protection
332
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...