18.8.2.2
Identification
GUID-3E1AB624-1B68-4018-B1BA-BC2C811F8F74 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measurands for IEC 60870-5-103
I103MEAS
-
-
18.8.2.3
Function block
GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v2
ANSI10000287-1-en.vsd
I103MEAS
BLOCK
I_A
I_B
I_C
IN
V_A
V_B
V_C
V_AB
V_N
P
Q
F
ANSI10000287 V1 EN-US
Figure 594: I103MEAS function block
18.8.2.4
Signals
PID-3972-INPUTSIGNALS v3
Table 860: I103MEAS Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of service value reporting
IA
REAL
0.0
Service value for current phase A
IB
REAL
0.0
Service value for current phase B
IC
REAL
0.0
Service value for current phase C
IN
REAL
0.0
Service value for residual current IN
VA
REAL
0.0
Service value for voltage phase A
VB
REAL
0.0
Service value for voltage phase B
VC
REAL
0.0
Service value for voltage phase C
V_AB
REAL
0.0
Service value for voltage phase-phase AB
V_N
REAL
0.0
Service value for residual voltage VN
P
REAL
0.0
Service value for active power
Q
REAL
0.0
Service value for reactive power
F
REAL
0.0
Service value for system frequency
Section 18
1MRK 502 066-UUS B
Station communication
1162
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...