Name
Values (Range)
Unit
Step
Default
Description
IMinOpPPZ1
10 - 6000
%IB
1
10
Minimum operate ph-ph current for Phase-
Phase loops, zone 1
IMinOpPGZ1
5 - 6000
%IB
1
10
minimum operate phase current for phase-
ground loops. zone 1
OpModePPZ2
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 2
OpModePGZ2
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 2
X1FwPPZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. reactance reach, Ph-Ph, zone
2, forward dir.
R1FwPPZ2
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-Ph, zone 2,
forward dir.
X1RvPPZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-Ph, zone 2,
reverse direction
X1FwPGZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. reactance reach, Ph-G, zone 2,
forward dir.
R1FwPGZ2
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-G, zone 2,
forward dir.
X0FwPGZ2
0.01 - 9000.00
Ohm/p
0.01
120.00
Zero seq. reactance reach, Ph-G, zone 2,
forward direction
R0FwPGZ2
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero seq. resistive reach, Ph-G, zone 2,
forward direction
X1RvPGZ2
0.01 - 3000.00
Ohm/p
0.01
40.00
Pos. seq. react. reach, Ph-G, zone 2, reverse
direction
RFPPZ2
0.01 - 9000.00
Ohm/l
0.01
30.00
Zero sequence reactance reach, zone 2
RFPGZ2
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-g, Zone 2
tPPZ2
0.000 - 60.000
s
0.001
0.400
Time delay to trip, Phase-Phase, zone 2
tPGZ2
0.000 - 60.000
s
0.001
0.400
Time delay to trip, Phase-Ground, zone 2
IMinOpPPZ2
10 - 6000
%IB
1
10
Time delay to trip, Phase-Phase, zone 2
IMinOpPGZ2
5 - 6000
%IB
1
10
Minimum operate phase current for phase
- ground loops, zone 2
OpModePPZ3
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 3
OpModePGZ3
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 3
DirModeZ3
Non-directional
Forward
Reverse
-
-
Forward
Time delay to trip, Phase-Phase, zone 2
X1FwPPZ3
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive seq. reactance reach, Ph-Ph, zone
3, zone direction
Table continues on next page
Section 7
1MRK 502 066-UUS B
Impedance protection
334
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...