ANSI09000149-4-en.vsd
AND
AND
AND
Bool to
integer
DLECND
STPG
STPP
IRELPG
IRELPP
BLOCK
AND
0
20ms
0
10ms
0
15ms
0
15ms
0
3
I
IMinPUPG
0
max
3 0
_
3
100
I BLK
PP
I
Iph
0
3
0.5
I
IMinPUPG
0
3 0
_
3
100
max
I Enable
PG
I
Iph
21 enable
LDEblock
AND
ANSI09000149 V4 EN-US
Figure 142: Phase-to-phase and phase-to-ground operating conditions (residual current
criteria)
A special attention is paid to correct phase selection at evolving faults. A PHSEL output signal is
created as a combination of the load encroachment characteristic and current criteria, refer to
figure
. This signal can be configured to STCND functional input signals of the distance
protection zone and this way influence the operation of the phase-to-phase and phase-to-ground
zone measuring elements and their phase related pickup and tripping signals.
Figure
presents schematically the composition of non-directional phase selective signals
NDIR_A (B or C). Internal signals ZMn and ZMmn (m and n change between A, B and C according to
the phase) represent the fulfilled operating criteria for each separate loop measuring element,
that is within the characteristic.
Section 7
1MRK 502 066-UUS B
Impedance protection
286
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...