arg
1
arg
set
p
AB
AB
ol
I
Z
V
V
b
-
×
=
-
ANSIEQUATION15027 V1 EN-US
(Equation 84)
where
AB
V
EQUATION1790-
ANSI V1 EN-US
is the voltage vector difference between phases A and B
AB
I
EQUATION1791-
ANSI V1 EN-US
is the current vector difference between phases A and B
Z
set
1
is the positive sequence impedance setting for phase-to-phase fault in zone direction
For Zone 1,
Z
R PPZ
j X PPZ
set
1
1
1
1
1
=
+ ⋅
IECEQUATION15011 V1 EN-US
(Equation 85)
where
R1PPZ1
is the positive sequence resistive reach for phase-to-phase fault for zone 1
X1PPZ1
is the positive sequence reactance reach for phase-to-phase fault for zone 1
For Zone 2-5 and RV
Z
R Zx
j X Zx
set
1
1
1
=
+ ⋅
IECEQUATION15012 V1 EN-US
(Equation 86)
where
R1Zx
is the positive sequence resistive reach for zone x (x=2-5 and RV)
X1Zx
is the positive sequence reactance reach for zone x (x=2-5 and RV)
V
pol
is the polarizing voltage
Operation occurs if 90°≤β≤270°
1MRK 502 066-UUS B
Section 7
Impedance protection
311
Technical manual