Vinj
Rshunt
GEN
Step-up
Transformer
95 % SEF
10
0
%
S
E
F
REX060/SIM module
REG670
5
6
8
3
1
7
9
I
V
Generator
R
N
2
Generator Protection Panel
ANSI11000067-1-en.vsd
4
10
U>
ANSI11000067 V1 EN-US
Figure 222: Example installation for stator injection
1
Generator unit consisting of a synchronous generator and a step-up transformer
2
Grounding resistor for the stator winding
3
Neutral point VT which is used as injection point and also to provide galvanic separation between primary
circuit and injection equipment
4
Cable used to inject the square-wave signal into the stator circuit
5
Connection for measurement of injected current. This signal is amplified in REX060 before it is given to
REG670 for evaluation.
6
Cable for measurement of injected voltage at the injection point. This signal is amplified in REX060 before it
is given to REG670 for evaluation.
7
Two VT inputs into REG670 which are used to measure injected current and voltage
8
Cable for 95% stator earth-fault protection
9
Separate VT input in REG670 used for 95% stator earth-fault protection
10
Protection for excessive over-voltages posed by generator. REX060 can withstand without damage
maximum voltage of 120V and when used together with REX062 up to 240V.
Section 7
1MRK 502 066-UUS B
Impedance protection
416
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...