7.8.5
Settings
PID-6564-SETTINGS v2
Table 142: ZMFPDIS (21) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of the function
RLdFwd
0.01 - 5000.00
Ohm/p
0.01
60.00
Resistance determining the load
impedance area - forward
RLdRvFactor
1 - 1000
%RLdF
w
1
100
Resistance factor determining the load
impedance area - reverse
XLd
0.01 - 10000.00
Ohm/p
0.01
400.00
Resistance determining the load
impedance area - forward
LdAngle
5 - 70
Deg
1
30
Angle determining the load impedance
area
CVTType
Any
Passive type
None (Magnetic)
-
-
Passive type
CVT selection determining filtering of the
function
OpModePPZ1
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 1
OpModePGZ1
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 1
X1PPZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Positive sequence reactance reach, Ph-Ph,
zone 1
R1PPZ1
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive sequence resistive reach, Ph-Ph,
zone 1
X1PGZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
positive sequence reactance reach, Ph-G,
zone 1
R1PZG1
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive sequence resistive reach, Ph-G,
zone 1
X0Z1
0.01 - 9000.00
Ohm/p
0.01
100.00
Zero sequence reactance reach, zone 1
R0Z1
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero sequence resistive reach, zone 1
RFPPZ1
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone 1
RFPGZ1
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-G, zone 1
tPPZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase-Phase, zone 1
tPGZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Ground-Earth, zone 1
IMinOpPPZ1
10 - 6000
%IB
1
10
Minimum operate ph-ph current for Phase-
Phase loops, zone 1
IMinOpPGZ1
5 - 6000
%IB
1
10
minimum operate phase current for phase-
ground loops. zone 1
OpModePPZ2
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 2
Table continues on next page
Section 7
1MRK 502 066-UUS B
Impedance protection
296
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...