en05000034.vsd
R
X
Forward
operation
Reverse
operation
IEC05000034 V1 EN-US
Figure 67: Typical quadrilateral distance protection zone with Phase selection with load
encroachment function FDPSPDIS (21) activated
The independent measurement of impedance for each fault loop together with a sensitive and
reliable built-in phase selection makes the function suitable in applications with single-phase
autoreclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at load exporting
end at phase-to-ground faults on heavily loaded power lines.
The distance protection zones can operate independently of each other in directional (forward or
reverse) or non-directional mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and cables in complex network
configurations, such as parallel lines, multi-terminal lines.
7.1.3
Function block
IP12800-1 v2
SEMOD115983-4 v8
ANSI06000256-2-en.vsd
ZMQPDIS (21)
I3P*
V3P*
BLOCK
LOVBZ
BLKTR
PHSEL
DIRCND
TRIP
TR_A
TR_B
TR_C
PICKUP
PU_A
PU_B
PU_C
PHPUND
ANSI06000256 V2 EN-US
Figure 68: ZMQPDIS (21) function block
Section 7
1MRK 502 066-UUS B
Impedance protection
178
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...