10.2.3
Function block
M14956-3 v5
ANSI06000280-2-en.vsd
SAPTOF (81)
V3P*
BLOCK
BLKTRIP
TRIP
PICKUP
BLKDMAGN
FREQ
ANSI06000280 V2 EN-US
Figure 364: SAPTOF (81) function block
10.2.4
Signals
PID-3897-INPUTSIGNALS v6
Table 386: SAPTOF (81H) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKTRIP
BOOLEAN
0
Blocking operate output
PID-3897-OUTPUTSIGNALS v6
Table 387: SAPTOF (81H) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
PICKUP
BOOLEAN
Common pickup signal
BLKDMAGN
BOOLEAN
Measurement blocked due to low amplitude
FREQ
REAL
Measured frequency
10.2.5
Settings
PID-3897-SETTINGS v6
Table 388: SAPTOF (81H) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
PUFrequency
35.00 - 90.00
Hz
0.01
51.20
Frequency set value
tDelay
0.000 - 60.000
s
0.001
0.000
Operate time delay
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset
Table 389: SAPTOF (81H) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Section 10
1MRK 502 066-UUS B
Frequency protection
672
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...