Time Accumulation
Transgression Supervision
Plus Retain
BLOCK
ACC_HOUR
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC15000322.vsd
Loop Delay
Loop Delay
tWarning
ACC_DAY
ADDTIME
tAddToTime
IEC15000322 V1 EN-US
Figure 573: TEILGAPC Simplified logic
TEILGAPC main functionalities
•
IN: Accumulation of the elapsed time when input IN is high
•
applicable to very long time accumulation (≤
99999.9 hours)
•
output
ACC_HOUR presents accumulated value in hours and ACC_DAY presents
accumulated value in days
•
accumulated value is retained in a non-volatile memory
•
any retained value is used as initiation value for the integration following by a restart
•
RESET: Reset of the accumulated value. Consequently all other outputs are also reset
•
independent of the input
IN value
•
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input
IN is high during the
reset.
•
reset can be made by activation of input
RESET or from LHMI or with IEC 61850
command
•
ADDTIME: Manually add time to the currently accumulated time
•
the amount of time to be added is defined by a setting
tAddToTime
•
time is added through activation of input
ADDTIME or from LHMI or with IEC 61850
command
•
BLOCK: Freeze the accumulation and block/reset the other outputs
•
independent of the input
IN value
•
BLOCK request overrides RESETrequest
•
Monitor and report the conditions of limit transgression
•
overflow if output
ACC_HOUR > 99 999.9 hours
•
alarm if output
ACC_HOUR > tAlarm
•
warning if output
ACC_HOUR > tWarning
1MRK 502 066-UUS B
Section 16
Monitoring
1099
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...