Fault tracing 601
7510
FBA A communication
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups
,
,
Check cable connections.
Check if communication master is able to
communicate.
7520
FBA B communication
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module B or between
PLC and fieldbus adapter
module B is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter group
.
Check cable connections.
Check if communication master is able to
communicate.
7580
INU-LSU comm loss
Programmable fault:
DDCS (fiber optic)
communication between
converters (for example, the
inverter unit and the supply
unit) is lost.
Check status of other converter
(parameter group
Check settings of parameter group
. Check the
corresponding settings in the control
program of the other converter.
Check cable connections. If necessary,
replace cables.
7581
DDCS controller
comm loss
Programmable fault:
DDCS controller comm
loss function
DDCS (fiber optic)
communication between drive
and external controller is lost.
Check status of controller. See user
documentation of controller.
Check settings of parameter group
.
Check cable connections. If necessary,
replace cables.
7582
MF comm loss
Programmable fault:
Master/follower
communication is lost.
See
(page
).
7583
Line side unit faulted
The supply unit (or other
converter) connected to the
inverter unit has generated a
fault.
The auxiliary code specifies the original
fault code in the supply unit control
program. Refer to the firmware manual of
the supply unit.
7584
LSU charge failed
The supply unit was not ready
(ie. the main contactor/breaker
could not be closed) within
expected time.
Check that communication to the supply
unit has been activated by
.
.
Check that the supply unit is enabled,
allowed to start, and can be controlled by
the inverter unit (eg. not in local control
mode).
8001
ULC underload fault
Programmable fault:
Selected signal has fallen
below the user underload
curve.
See
(page
).
Code
(hex)
Fault
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...