586 Fault tracing
AFE7
Follower
A follower drive has tripped.
Check the auxiliary code. Add 2 to the
code to find out the node address of the
faulted drive.
Correct the fault in the follower drive.
AFEA Enable start signal
missing
(Editable message text)
No enable start signal
received.
Check the setting of (and the source
selected by) parameter
.
AFEB Run enable missing
(Editable message text)
No run enable signal is
received.
Check setting of parameter
. Switch signal on (e.g. in
the fieldbus Control Word) or check
wiring of selected source.
AFEC External power signal
missing
but no
voltage is connected to the
XPOW connector of the control
unit.
Check the external 24 V DC power
supply to the control unit, or change the
setting of parameter
AFF6
Identification run
Motor ID run will occur at next
start, or is in progress.
Informative warning.
AFF7
Autophasing
Autophasing will occur at next
start.
Informative warning.
B5A0
STO event
Programmable event:
Safe torque off function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual and description of
parameter
(page
).
B5A4
SW internal
diagnostics
Control unit rebooted
unexpectedly.
Informative event.
B686
Checksum mismatch
Programmable event:
The calculated parameter
checksum does not match any
enabled reference checksum.
See
(page
D200
Cleaning max warning Maximum number of cleanings
in defined time frame has been
exceeded.
Check parameters
(page
) for clean maximum protection
settings.
D201
U/f curve settings
invalid
U/f curve frequency points are
not defined in proper
ascending order.
(page
D205
Underload
Underload supervision signal
exceeded the defined
underload supervision limit.
Check parameters in group
(page
).
D207
Restart delay
Restart delay is active - The
drive start command is
inhibited for the time set in
parameter
.
Check parameters
D208
Overload
Overload supervision signal
exceeded the defined overload
supervision limit.
Check parameters
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...