![ABB ACS880-01 Series Скачать руководство пользователя страница 200](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621200.webp)
200 Parameters
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
0.000 mA or
V
-22.000 … 22.000
mA or V
Minimum value of AI2.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
.
20.000 mA or
10.000 V
-22.000 … 22.000
mA or V
Maximum value of AI2.
1000 = 1 mA
or V
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
.
(Changing the polarity settings of
can
effectively invert the analog input.)
0.000
-32768.000 …
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter
.
See the drawing at parameter
.
100.000
-32768.000 …
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
13
Configuration of standard analog outputs.
Displays the value of AO1 in mA.
This parameter is read-only.
-
0.000 … 22.000 mA Value of AO1.
1000 = 1 mA
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
Zero
None.
0
Motor speed used
(page
1
Output frequency
(page
).
3
Motor current
(page
4
No.
Name/Value
Description
Def
/
FbEq16
AI
in
AI
scaled
)
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...