![ABB ACS880-01 Series Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621119.webp)
Program features 119
Thermal protection of motor cable
The control program contains a thermal protection function for the motor cable. This
function should be used, for example, when the nominal current of the drive exceeds
the current-carrying capacity of the motor cable.
The program calculates the temperature of the cable on the basis of the following
data:
• Measured output current (parameter
)
• Nominal continuous current rating of the cable, specified by
, and
• Thermal time constant of the cable, specified by
When the calculated temperature of the cable reaches 102% of the rated maximum,
a warning (
) is given. The drive trips on a fault (
) when 106% is reached.
Settings
Parameters
…
(page
User load curve
The user load curve provides a function that monitors an input signal (eg. motor
torque or motor current) as a function of drive output speed or frequency. The
function includes both high limit (overload) and low limit (underload) monitoring.
Overload monitoring can, for example, be used to detect a pump becoming clogged
or a saw blade hitting a knot. Underload monitoring can detect the load being lost, for
example because of the snapping of a transmission belt.
The monitoring is effective within a motor speed and/or frequency range. The
frequency range is used with a frequency reference in scalar motor control mode;
otherwise, the speed range is used. The range is defined by five speed (parameters
) or frequency (
…
) values. The values are positive, but the
monitoring is symmetrically active in the negative direction as the sign of the
monitored signal is ignored. Outside the speed/frequency range, the monitoring is
disabled.
An underload (
…
) limit is set for each of the
five speed or frequency points. Between these points, the limits are interpolated
linearly to form overload and underload curves.
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...