![ABB ACS880-01 Series Скачать руководство пользователя страница 424](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621424.webp)
424 Parameters
Acceleration
assistance speed
limit
Defines the speed limit at which acceleration assistance is
automatically disabled.
The assistance current boost is produced only once. If the
speed is below the value set in the parameter, then no
repeated current boost is applied.
20.0
0.0...100.0 %
Acceleration assistance speed limit.
10 = 1%
Acceleration
assistance current
Defines motor current reference used when the acceleration
assistance routine is active.
100.0
0.0...300.0 %
Acceleration assistance current.
10 = 1%
Defines the source for Kick-start enable signal.
For further information, see section
Not selected
Kick start enable is inactive.
0
Selected
Kick start enable is active.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
8
DIO2
Digital input/output DIO2 (
, bit 1).
9
ESP CW bit 5
, bit-5 status controls
enable/disable status of the function.
10
Source selection (see
).
Defines the time period for a drive to keep modulating at
speed defined with parameter
2.0
0.0...30.0 s
Kick start hold time.
10 = 1s
Defines the speed reference used to perform kick-start
routine.
4.0
4.0...100.0 %
Kick start speed reference.
10 = 1%
Defines the motor current reference used when the kick-start
routine is active.
This current produces higher starting torque necessary for the
motor to overcome static friction and starting spinning.
100.0
0.0...300.0 %
Kick start current ref.
10 = 1%
Defines the kick-start reference change rate facilitating
gradual increase of motor current.
100.0
0.0...1000.0 %/s
Kick start current ramp.
10 = 1%
Current pulse start
mode enable
Defines the source for the current pulse-start enable signal.
For further information, see section
(page
Not selected
Current pulse start mode enable is inactive.
0
Selected
Current pulse start mode enable is active.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...