246 Parameters
Activates/deactivates the DC hold and post-magnetization
functions. See section
(page
).
Notes:
• These functions are only available in speed control in DTC
motor control mode (see page
).
• DC magnetization causes the motor to heat up. In
applications where long DC magnetization times are
required, externally ventilated motors should be used. If
the DC magnetization period is long, DC magnetization
cannot prevent the motor shaft from rotating if a constant
load is applied to the motor.
0000b
0000b…0011b
DC magnetization selection.
1 = 1
Defines the DC hold speed. See parameter
(page
).
5.00 rpm
0.00 … 1000.00
rpm
DC hold speed.
See par.
Defines the DC hold current in percent of the motor nominal
current. See parameter
, and section
).
30.0%
0.0 … 100.0%
DC hold current.
1 = 1%
Defines the length of time for which post-magnetization is
active after stopping the motor. The magnetization current is
defined by parameter
.
See parameter
0 s
0…3000 s
Post-magnetization time.
1 = 1 s
Continuous
magnetization
command
Activates/deactivates (or selects a source that
activates/deactivates) continuous magnetization. See section
The magnetization current is calculated on the basis of flux
reference (see parameter group
).
Notes:
• This function is only available when ramping is the
selected stop mode (see parameter
), and
only in speed control in DTC motor control mode (see page
• Continuous magnetization causes the motor to heat up. In
applications where long magnetization times are required,
externally ventilated motors should be used.
• Continuous magnetization may not be able to prevent the
motor shaft from rotating during a long period if a constant
load is applied to the motor.
0 = Normal operation
1 = Magnetization active
Off
0.
0
No.
Name/Value
Description
Def
/
FbEq16
Bit
Value
0
1 = Enable DC hold. See section
Note:
The DC hold function has no effect if the start signal is switched off.
1
1 = Enable post-magnetization. See section
(page
).
Note:
Post-magnetization is only available when ramping is the selected stop mode (see
parameter
2…15
Reserved
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...