Parameters 183
09
ESP signals to monitor the pump.
Displays the current state of the ESP application functions.
Displays the current state of drive control.
Drive not ready
Drive is not ready for operation.
0
ID run undone
No motor ID run done. Necessary to run in DTC mode.
1
Drive stopped
Drive is stopped.
2
Fault active
A fault is active.
3
Local control
Drive is in Local control.
4
Jog mode
Jogging enable signal is On.
5
Ext1 running
Control location EXT1 is active.
6
Ext2 running
Control location EXT2 is active.
7
Stopping
Drive is stopping the motor as per deceleration ramp time
settings.
8
Em stop active
Stopping after receiving an emergency stop command.
9
Constant speed
Drive is running in constant speed mode.
10
Displays actual drive output current.
0.00
0.00...30000.00 A
Drive output current.
10 = 1A
Displays the actual motor current estimate based on
transformer ratio and sine-filter settings.
0.00
0.00...30000.00 A
Estimated motor current.
10 = 1A
Displays estimated actual motor current in %.
0.00
0.00...30000.00 %
Estimated motor current.
10 = 1%
Displays the actual motor voltage estimate based on
transformer ratio setting.
0.00
0.00...30000.00 V
Estimated motor voltage.
10 = 1V
Displays the frequency reference currently produced by the
ESP control program.
0.00
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Production state
Drive is following the ESP program reference.
1
Restart delay act
Restart delay timer active.
2
Backspin observer act Backspin speed observer routine is active.
3...4
Reserved
5
Kick-start act
Kick-start starting routine is active.
6
Current pulse act
Current-pulse starting routine is active.
7
Underload act
Underload condition is active.
8
Overload act
Overload condition is active.
9...10
Reserved
11
Current boost/IR
comp. act
Voltage or current boost is active.
12
Cleaning act
Pump cleaning operation is active.
13...14 Reserved
15
Time control act
Time control is active.
Содержание ACS880-01 Series
Страница 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Introduction to the manual ...
Страница 22: ...22 Using the control panel ...
Страница 28: ...28 Control locations and operating modes ...
Страница 145: ...Application macros 145 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 146: ...146 Application macros ...
Страница 502: ...502 Parameters ...
Страница 606: ...606 Fault tracing ...
Страница 662: ...662 Control chain diagrams ...
Страница 664: ...Contact us www abb com drives www abb com drivespartners 3AXD50000041193 Rev A EN EFFECTIVE 2017 06 30 ...